Comtech EF Data CLO-10 User Manual

Page 107

Advertising
background image

CLO-10 Link Optimizer

Revision 1

Redundant System Operation

MN/CLO-10.IOM

From the Remote Control submenu, select Serial using the ◄ ► arrow keys, then press

ENTER

:

Remote Control: Local

Serial Ethernet (◄ ► ENT)

Next, select Interface using the ◄ ► arrow keys, then press

ENTER

. Here, the user is further

prompted to enter the bus address.

Serial Config: Interface

Baudrate (◄ ► ENT)

Serial Interface: RS232

RS485-2W RS485-4W (ENT)

Once the Serial Interface submenu is displayed, select RS485-2W (2-wire) or RS485-4W (4-
wire) using the ◄ ► arrow keys, then press

ENTER

.

If this unit is properly configured as a Redundant Unit, and the Redundant feature has been
properly enabled
, the user is prompted as follows:

RS-485 Bus Address: 1000

(▲ ▼ ENT)

Select the RS-485 bus address of this unit using the c d arrow keys. Valid address values are
limited to 1000, 3000, 5000, and 7000.

Once the bus address is edited, the user should press ENTER.

A–23

Advertising