1 config: remote, Config: remote ( serial, Config: remote ( serial ( interface – Comtech EF Data CLO-10 User Manual

Page 64: Config: remote æ serial, Config: remote æ serial æ interface

Advertising
background image

CLO-10 Link Optimizer

Revision 1

Front Panel Operation

MN/CLO-10.IOM

6.4.1 CONFIG: Remote

Remote Control: Local

Serial Ethernet (◄ ► ENT)

Select Local, Serial, or Ethernet using the ◄ ► arrow keys, then press

ENTER

. If Local is

selected, then remote control is disabled. Remote monitoring is still possible.

CONFIG: Remote Æ Serial

If Serial is selected:

Serial Config: Interface

Baudrate (◄ ► ENT)

CONFIG: Remote Æ Serial Æ Interface

If Interface is selected:

Serial Interface: RS232

RS485-2W RS485-4W (ENT)

Select RS232, RS485-2W (2-wire) or RS485-4W (4-wire) using the ◄ ► arrow keys, then press

ENTER

. Here, the user is further prompted to enter the bus address.

If RS232 is selected, the following menu is displayed:

In RS-232 Mode, Serial Bus

Base Address is fixed @ 0000

CONFIG: Remote Æ Serial Æ Interface Æ RS485-2W or RS485-4W

IMPORTANT

If the unit is configured as a Redundant Unit and the Redundant feature has
been enabled, refer to

Appendix A. REDUNDANCY SYSTEM OPERATION for

detailed information on the front panel operations associated with redundancy.

If either RS-485 mode is selected, and this unit is not configured as a Redundant Unit and the
Redundant feature has not been enabled, the user is further prompted:

RS-485 Bus Address: 0245

(◄ ► ▲ ▼ ENT)

Edit the RS-485 bus address of this unit by selecting the digit to be edited using the

ef

arrow

keys. The value of the digit is then changed using the d c arrow keys. The valid range of
addresses is from 1 to 9996.

Once the bus address is edited, the user should press ENTER.

6–8

Advertising