Rs-485 communication – Wavetronix Click 500 (programmable controller) (CLK-500) - User Guide User Manual

Page 21

Advertising
background image

20

CHAPTER 3 WIRING THE DEVICES

Figure 3.1 – Removing and Wiring Screw Terminal Blocks

RS-485 Communication

All Click series devices have RS-485 communication capabilities. RS-485 is important for

Click devices because it is carried on the T-bus to all the Click devices on a given DIN rail.

Connecting RS-485 communications to the Click devices on a DIN rail can be accom-

plished in two different ways: through a 5-screw terminal on the end of a T-bus, or through

a Click module, which will then communicate with the T-bus.

Note

The steps in this section are specifically for use with a Wavetronix SmartSensor ca-
ble. If you are using a different cable or wiring system, the colors of the wires used
will be different.

To connect through a 5-screw terminal, follow these steps.
1 Connect the +485 (white) wire from the terminal block or cable to the middle screw

terminal on the 5-screw terminal block connector you’re using for the T-bus in question

(see Figure 2.2 in the previous chapter for the pinout of the 5-screw terminal block).

2 Connect the -485 (blue) wire from the terminal block or cable to the middle screw

terminal on the 5-screw terminal block.

3 Plug the 5-screw terminal block into the T-bus.

To connect through any Click device with RS-485 ports, follow these steps:
1 Ensure that the Click device is mounted on a T-bus connector.

2 Connect the +485 (white) wire from the terminal block or cable to the terminal marked

“+485” in the screw terminal blocks (see Figure 3.2).

3 Connect the -485 (blue) wire from the terminal block or cable to the terminal marked

“-485” in the screw terminal blocks.

4 Connect the RS-485 drain wire from the terminal block or cable to a GND terminal in

the screw terminal blocks.

Advertising