F4-06 Analog output channel 2 bias

-

±109.2

0.0

A

F5

DO-02 Setup

F5-01 DO-02C digital output channel 1 selection

0: During RUN 1

1: Zero speed

2: Fref/Fout agree 1

3: Fref/Set agree 1

4: Frequency detection 1

5: Frequency detection 2

6: Inverter Ready

7: DC bus undervoltage

8: Baseblock 1

9: Option reference

A: Remote operation

B: Torque detection 1 (N.O.)

C: Loss of reference

D: DB overheat

E. Fault

F: Not used

10: Minor fault

11: Reset command active

12: Timer output

13: Fref/Fout agree 2

14: Fref/Set agree 2

15: Frequency detection 3

16: Frequency detection 4

17: Torque detection 1 (N.C.)

18: Torque detection 2 (N.O.)

19: Torque detection 2 (N.C.)

1A: Reverse direction

1B: Baseblock 2

1D: Regenerating

1E: Restart enabled

1F: Overload (OL1)

20: OH prealarm

30: Current/Torque limit

31: Speed limit

37: During RUN 2

-

0~FF

0

A

F5-02 DO-02C digital output Channel 2 selection

(same as F5-01)

-

0~3F

1

A

F6

DO-08 Set-up

F6-01 DO-08 digital output selection

0: 8-channel Individual

1: Binary Output

-

0/1

0

A

F8

PG-P2/H2 Set-up

F8-01 Speed feedback method selection

0: Encoder inputs 1: Hall sensor input

-

0/1

1

Q

F8-02 Pulse train moving average value

0=1 Scan (5msec)

-

0-50

0

B

F9

CP-916 Set-up

F9-01 External fault input level from communication option

-

0/1

0

A

F9-02 External fault from communication level

-

0/1

0

A

F9-03 Operation at external fault input from communication option

0: Ramp to stop

2: Fast-stop

1: Coast to stop

3: Alarm only

-

0~3

1

A

No.

Parameter Description

Unit

Setting Range

Default

Access

Level

User

Setting

Appendix

VS-616PS5 Parameter List