Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 36

Advertising
background image

36

VS-616PS5 Programming Manual

Note: Setting units for D1-01 to D1-09 are dependent upon the setting of digital operator display mode

(O1-03). Possible setting units include Hz, percentage, RPM, or engineering units. See section
O1, Monitor Selection, for more details.

Multi-step Speed Ref. 1

Frequency

Reference

FWD (REV) Run/Stop

(Terminal 5)

Multi-step Speed Ref. 2

(Terminal 6)

D1-04

40.0Hz

D1-01

10.0Hz

D1-02

20.0Hz

D1-03

30.0Hz

ON

ON

ON

ON

Figure 24 Multi-step Speed Operation - Timing Diagram

Multi-step Speed Ref. 3

(Terminal 7)

Jog Ref.

(Terminal 8)

ON

ON

ON

ON

ON

D1-05

45.0Hz

D1-06

50.0Hz

D1-07

55.0Hz

D1-08

60.0Hz

D1-09

6.0Hz

Time

Section D: Reference Parameters

D1 Reference Limits