Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 63

Advertising
background image

VS-616PS5 Programming Manual

63

.

Notes:

1. When both a hold reference memory selection (D4-01 = “1”) and an accel/

decel hold command are input, a stop command followed by a run command
will generate storage of the output frequency data until the accel/decel stop
command is released. Operation resumes after the frequency storage.

2. When the power supply is turned OFF after the accel/decel hold command is

input, the held output frequency is also stored.

3. When D4-01 is set to “0,” the held output frequency is not stored.

• Inverter Overheat OH2 Alarm (setting: “B”)

Inputting the inverter overheat alarm signal, “OH2” blinks on the digital operator dis-
play (Alarm condition only). The user can connect the dry contact of an external
heat sensor for indication of device over-temperature. To close an output contact
under this condition, set a multi-function contact output (H2-XX) to “20”.

• Multi-function Analog Input Enable/Disable (setting: “C”)

This setting allows terminal 16 multi-function analog input to be enabled (accepted)
or disabled (disregarded) via a digital input.

Open:

Terminal 16 command is not accepted.

Closed:

Terminal 16 command is accepted.

• Speed Control Integral Value Reset (setting: “E”)

This function allows the speed control integral value to be reset while the inverter is
running.

Open:

PI-control (adds the speed control integral values.)

Closed:

P-control (resets the speed control integral values by the integral time
constant).

OFF

ON

OFF

ON

ON

OFF

OFF

Fwd Run

Accel/Decel

Output

Hold Command

Frequency

Figure 32 Accel/Decel Hold Command Timing Diagram

Frequency

Reference

Section H: Control Circuit Terminal Parameters

H1 Digital Inputs

Advertising