Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 89

Advertising
background image

VS-616PS5 Programming Manual

89

Setting Range:

0 to 300%

Factory Default:

150%

Sets the overtorque detection level as a percentage of motor rated torque.

Setting Range:

0.0 to 10.0s

Factory Default:

0.1s

The overtorque detection time sets the time for which the motor current (or torque)
must exceed the overtorque detection level (L6-02) before the overtorque condition is
acknowledged as a valid overtorque condition. The digital operator then displays
“OL3.”

Activates overtorque detection 2, and selects whether detection generates an alarm
or a fault.

Overtorque detection 2 functions the same as overtorque detection 1 (L6-01), except
that “OL4” is displayed on the digital operator instead. This function is used when two
levels of detection are required.

Setting Range:

0 to 300%

Factory Default:

150%

Sets the second overtorque detection level as a percentage of motor rated torque.

L6-02 Overtorque Detection 1 Level

B

L6-03 Overtorque Detection 1 Time

B

L6-04 Overtorque Detection 2 Selection

A

Setting

Description

0

Overtorque detection is disabled (factory default).

1

Overtorque detection is enabled whenever at the speed agree level (when inverter is not accel-

erating or decelerating). Continue running after detection (OL4 alarm).

2

Overtorque detection is enabled always. Continue running after detection (OL4 alarm).

3

Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detec-

tion (OL4 fault).

4

Overtorque detection is enabled always. Coast to a stop after detection (OL4 fault).

L6-05 Overtorque Detection 2 Level

A

Section L: Protection Parameters

L6 Torque Detection