55

Setting Range:

±300.0

Factory Default:

1.0

Sets the channel 1 output gain for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in this parameter (F4-02).

Setting Range:

±109.2%

Factory Default:

0.0%

Sets the channel 1 output bias for the analog output monitors. To determine the out-
put level, add the bias value set in F4-03 to the monitor output level.

Setting Range:

Same as F4-01

Factory Default:

Inverter output current (setting = “3”)

Select the analog output monitors for channel 2 of the AO-08 and AO-12 options.
Select from the table included in parameter F4-01.

Setting Range:

±300.0

Factory Default:

1.0

This parameter sets the channel 2 output gain for the analog output monitors. To
determine the output level, multiply the monitor output level by the gain value set in
this parameter F4-05.

Setting Range:

±109.2%

Factory Default:

0.0%

Sets the channel 2 output bias for the analog output monitors. To determine the out-
put level, add the bias value set in F4-06 to the monitor output level.

F4-02 Analog Output Channel 1 Gain

A

F4-03 Analog Output Channel 1Bias

A

F4-04 Analog Output Channel 2 Selection

A

F4-05 Analog Output Channel 2 Gain

A

F4-06 Analog Output Channel 2 Bias

A