Selects the stopping method after a transmission error is detected.
H5-05 enables or disables the MODBUS time out detection function. After initial com-
munication begins, if communication is interrupted for longer than 2 seconds, then a
communication fault will occur.
During a communication fault, the following fault code will be displayed: “bus”.
H5-04 Stopping Method After Communication Error
A
Setting
Description
0
Ramp to stop according to the time set in C1-02.
1
Fast-stop according to the time set in C1-09.
2
Coast to stop
3
Alarm only, continuous operation (factory default)
H5-05 MODBUS Time Out Detection
A
Setting
Description
0
Disabled - Time out detection is disabled.
1
Enabled - Time out detection is enabled.
Section H: Control Circuit Terminal Parameters
H5 Modbus Communication Parameters