Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 81

Advertising
background image

VS-616PS5 Programming Manual

81

Selects the stopping method after a transmission error is detected.

H5-05 enables or disables the MODBUS time out detection function. After initial com-
munication begins, if communication is interrupted for longer than 2 seconds, then a
communication fault will occur.
During a communication fault, the following fault code will be displayed: “bus”.

H5-04 Stopping Method After Communication Error

A

Setting

Description

0

Ramp to stop according to the time set in C1-02.

1

Fast-stop according to the time set in C1-09.

2

Coast to stop

3

Alarm only, continuous operation (factory default)

H5-05 MODBUS Time Out Detection

A

Setting

Description

0

Disabled - Time out detection is disabled.

1

Enabled - Time out detection is enabled.

Section H: Control Circuit Terminal Parameters

H5 Modbus Communication Parameters