VS-616PS5 Programming Manual
F2
AI-14B Set-up
Sets CH1 to CH3 input functions when AI-14B option is connected.
When the 3CH individual input selection is used, set parameter B1-01 to “1” (fre-
quency reference from control circuit terminal). The option/inverter reference selec-
tion, which is selected by a multi-function contact input (H1-XX = “2”), is disabled
when using the AI-14B option.
F2-01 AI-14B Function Selection
A
Setting
Function
CH1 (TC1 to TC4)
CH2 (TC2 to TC4)
CH3 (TC3 to TC4)
0
3-channel individual
input (factory default)
Substitute for
terminals 13 & 17
Substitute for
terminals 14 & 17
Substitute for
terminals 16 & 17
1
3-channel additional
input
Sum of CH1 to CH3 input values is used as the speed
reference value. (Reference the AI-14B instruction manual for
details).
Section F: Option Parameters