VS-616PS5 Programming Manual

51

Setting Range:

0 to 50%

Factory Default:

10%

This sets the excessive speed deviation detection level as a percentage of maximum
output speed (E1-06). Used in conjunction with parameter F1-11 to sense a speed
deviation condition.

Setting Range:

0.0 to 10.0s

Factory Default:

0.5s

This parameter sets the elapsed time for which a speed deviation condition must
exist, before a fault (or alarm) is generated.

A fault (or alarm) signal is output after the deviation between speed reference and the
actual motor speed exceeds the set value of F1-10 and after the time set to F1-11
elapses. The stopping method is set with F1-04. Also, detection is not activated
while accelerating/decelerating or during torque control.

Setting Range:

0.0 to 10.0s

Factory Default:

3.0s

This sets the time for which a PG open condition must exist, before a fault (or alarm)
is generated.

The stopping method, when a “PGO” condition is detected, is selected by param-
eter F1-02.

F1-10 PG Deviation Detection Level

A

F1-11 PG Deviation Detection Time

A

F1-13 PG Open Detection Delay Time

A

Figure 30 Overspeed Detection Timing Diagram

Speed Reference

OFF

ON

Motor Speed

F1-10

Speed Deviation

Fault Signal

F1-11

OFF

Section F: Option Parameters

F1 PG Option Set-up