VS-616PS5 Programming Manual

17

B4

Delay Timers
Use the inverter input (multifunction inputs) and output (multifunction outputs) in
place of an external timer. When a multi-function contact input (H1-XX = “18”) is
closed, a multi-function contact output (H2-XX = “12”) can be set to close after the
On-delay time (B4-01) has expired. This function operates independently of any con-
current inverter activity.

Setting Range:

0.0 to 300.0s

Factory Default:

0.0s

Sets the ON-delay time in units of 0.1 second. The multi-function input must be
“closed” for longer than the ON-delay timer for the multi-function output to close.

Setting Range:

0.0 to 300.0s

Factory Default:

0.0s

Sets the OFF-delay time in units of 0.1 second. The multi-function input must be
“open” longer than the OFF-delay timer for the multi-function output to open.

B4-01 On-delay Timer

A

B4-02 Off-delay Timer

A

Multi-function Contact
Input: Timer Function

Multi-function Contact

Output: Timer Function

ON

ON

B4-01

Figure 8 Timing Diagram of Timer Function

B4-01

B4-02

ON ON ON

ON

ON ON ON

ON

B4-02

Section B: Application Parameters

B4 Delay Timers