VS-616PS5 Programming Manual

H

Control Circuit Terminal Parameters

H5

Modbus Communication Parameters
The inverter uses communication port 6CN to communicate via MODBUS protocol.

Setting Range: 0 to 1F
Factory Default:1F

Selects a station address for identification of the inverter during serial communica-
tion.

Selects the baud rate at which the inverter serially communicates with external
devices.

Selects the transmission parity for the 6CN MODBUS port.

H5-01 Serial Communication Station Address

A

H5-02 Serial Communication Baud Rate

A

Setting

Description

0

1200 Baud per Second

1

2400 Baud per Second

2

4800 Baud per Second

3

9600 Baud per Second (factory default)

4

19200 Baud

<1110>

H5-03 Serial Communication Parity Selection

A

Setting

Description

0

No parity (factory default)

1

Even parity

2

Odd parity

Section H: Control Circuit Terminal Parameters

H5 Modbus Communication Parameters