Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 110

Advertising
background image

110

VS-616PS5 Programming Manual

H5-03 Serial communication speed selection

0: No parity, 1: Even parity, 2: Odd parity

1

0-2

0

A

H5-04 Stopping method after communication error

0: Ramp to stop, 1: Coast to stop, 2: Fast stop, 3: Alarm only

1

0-3

3

A

H5-05 Serial communication timeover detection

0: Disabled , 1: Enabled

1

0,1

1

A

L

Protection Parameters

L2

Power Loss Ride through

L2-01 Momentary power loss ride through

0: Disabled

-

0

0

B

L2-02* Momentary power loss ride through time

s

0.0~2.0

0.7

B

L2-05 Undervoltage detection level

V

150~210

190

A

L3

Stall Prevention/Current Limit

L3-01 Overvoltage protection (stall prevention during decel)

0: Disabled

1: Enabled

-

0~1

1

B

L4

Reference Detection

L4-01 Speed agree detection level (without sign)

%

0.0~100.0

0.0

B

L4-02 Speed agree detection width

%

0.0~100.0

2.0

B

L4-03 Speed agree detection level (with sign)

%

0~±100.0

0.0

A

L4-04 Speed agree detection width

%

0.0~100.0

2.0

A

L4-05 Operation when frequency reference is missing

0: Stop

1: Run at 80% of previous reference

-

0/1

0

A

L5

Fault Restart

L5-01 Number of automatic restart attempts

-

0~10

0

B

L5-02 Automatic restart operation selection

0: No fault relay

1: Fault relay active

-

0/1

0

B

L6

Torque Detection

L6-01 Overtorque detection 1 selection

0: Disabled

3: Fault at speed agree

1: Alarm at speed agree

4: Fault at run

2: Alarm at run

-

0~4

0

B

L6-02 Overtorque detection 1 level

%

0~300

150

B

L6-03 Overtorque detection 1 time

s

0.0~10.0

0.1

B

L6-04 Overtorque detection 2 selection

0: Disabled

3: Fault at speed agree

1: Alarm at speed agree

4: Fault at run

2: Alarm at run

-

0~4

0

A

L6-05 Overtorque detection 2 level

%

0~300

150

A

L6-06 Overtorque detection 2 time

s

0.0~10.0

0.1

A

L7

Torque Limit

L7-01 Forward torque limit

%

0~300

150

B

L7-02 Reverse torque limit

%

0~300

150

B

L7-03 Regenerative forward torque limit

%

0~300

150

B

L7-04 Regenerative reverse torque limit

%

0~300

150

B

L8

Hardware Protection

L8-01 Protection selection for internal DB resistor

0: Not Provided

1: Provided

-

0/1

0

A

L8-02 OH pre-alarm level

ºC

50~110

95

A

No.

Parameter Description

Unit

Setting Range

Default

Access

Level

User

Setting

Appendix

VS-616PS5 Parameter List

Advertising