Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 50

Advertising
background image

50

VS-616PS5 Programming Manual

Sets the relationship between the motor rotation direction and PG polarity. (Hall sen-
sor HS4 & HS5 or encoder channel A & B).

The motor’s rotation direction applies when viewing the motor shaft from the load
side.

Setting Range:

0 to 120%

Factory Default:

115%

This parameter sets the motor overspeed detection level as a percentage of maxi-
mum output speed (E1-06). Used in conjunction with parameter F1-09 to sense an
overspeed condition.

Setting Range:

0.0 to 2.0s

Factory Default:

0.0s

Sets the elapsed time from when an overspeed condition is detected to when a fault
(or alarm) occurs.

A fault signal is output to stop operation after the absolute value of the motor speed
exceeds the set value of F1-08 for the time set to F1-09. The stopping method is set
by F1-03.

F1-05 PG Rotation Selection

Q

Setting

Description

0

HS5 leads HS4 (channel B leads A) in FWD direction.

1

HS4 leads HS5 (A leads B) in FWD direction (factory default).

F1-08 Overspeed Detection Level

A

F1-09 Overspeed Detection Time

A

Figure 29 Overspeed Detection Timing Diagram

Overspeed Level (F1-08)

OFF

ON

|

Motor Speed

|

F1-09

Overspeed Fault Signal

0

Section F: Option Parameters

F1 PG Option Set-up