Section L: Protection Parameters

L8 Hardware Protection

Input phase loss detection is disabled in the following cases:
• A Stop command is input
• Magnetic Contact (MC) shuts OFF
• CPU A/D converter fault (CPF5)
• During deceleration
• Output current

30% of Inverter rated current

This parameter detects the inverter output open-phase.

An open phase condition may be erroneously detected

at the output

if inadequate

motor capacity is applied to the inverter, or the load torque is low.

The ground fault detection circuit monitors the output current and activates when
excessive ground current is detected.

A ground fault will occur when the inverter output grounding current has exceeded
50% of the inverter rated current.

L8-07 Output Phase Loss Protection

A

Setting

Description

0

Inverter output open-phase detection is disabled (factory default).

1

Inverter output open-phase detection is enabled.

L8-10 Ground Fault Protection

A

Setting

Description

0

Ground fault detection is disabled

1

Ground fault detection is enabled.(factory

default).