VS-616PS5 Programming Manual

Section H: Control Circuit Terminal Parameters

H2 Digital Outputs

• During Run (setting: “0”)

Closes after a run command is inputted or when the inverter generates output volt-
age.

• Zero-speed (setting: “1”)

Closes when the motor speed is less than the zero-speed level (B2-01).

• Speed Agree 1 (setting: “2”)

Closes whenever the output speed “agrees” with the speed reference plus or minus
the speed agree detection width (L4-02). This works in both forward and reverse
operation.

• Desired Speed Agree 1 (setting: “3”)

Closes whenever the output Speed “agrees” with the Speed Agree Detection Level,
(L4-01), plus or minus the Speed Agree Detection Width, (L4-02). This works in
both forward and reverse operation.

Detection Width 1 (L4-02)

Output Speed

Speed Agree 1 Signal

ON

Speed Reference

Figure 37 Speed Agree Signal 1 Timing Diagram

OFF

OFF

Detection Width 1 (L4-02)

Output Speed

Desired Speed

ON

Detection Level 1 (L4-01)

Figure 38 Desired Speed Agree 1 Signal Timing Diagram

Agree 1 Signal

OFF

OFF