Main Menu:Initialize <ENTER>

A

Initialization Parameters

A1

Initialization Set-up

This parameter allows the “masking” of parameters according to user level. See the
following table:

Use this parameter to reset the inverter to its factory default settings. Initialize the
inverter after changing the control PCB, or after selecting inverter capacity (O2-04).

This parameter allows password entry to view masked parameters.

A1-01 Parameter Access Level

Q

Setting

Description

0

Operation Only

2

Quick Start Level (factory default) - For maintenance-level programming.

3

Basic Level - For basic programming in most applications.

4

Advanced Level - For advanced programming in special applications.

A1-03 Operator Status

Q

Setting

Description

0

No Initialization (factory default).

2220

2-Wire Initialization - terminal 1 becomes FWD run command and

terminal 2 becomes REV run command. All other parameters are

reset to their original factory default settings.

3330

3-Wire Initialization - terminal 1 becomes run command, terminal 2

becomes stop command and terminal 3 becomes FWD/REV run

selection. All other parameters are reset to their original factory

default settings.

A1-04 Password Entry

Q

Section A: Initialization Parameters

A1 Initialization Set-up