O2-01 local/remote key b, O2-04 inverter model selection a – Yaskawa VS-616PS5 Series Programming Manual User Manual

Page 97

Advertising
background image

VS-616PS5 Programming Manual

97

O2

Key Selection

Enables/disables the digital operator LOCAL/REMOTE key.

Enables/disables the digital operator STOP key, during operation from the external
terminals and during serial communication.

Setting Range:

00 to FF

Factory Default:

Inverter model dependent, kVA dependent

Sets the inverter capacity, according to the model number. Control parameters with
defaults specific to the inverter’s capacity are set automatically (i.e. carrier frequency,
motor data, etc.). This parameter does not need changing, unless the control board
is replaced. When replacing the control board, set parameter 02-04 to the appropriate
value per the following tables and re-initialize with parameter A1-03.

230 V Models

O2-01 Local/Remote Key

B

Setting

Description

0

Local/Remote key is disabled.

1

Local/Remote key is enabled (factory default).

Depressing the Local/Remote key switches operation commands

between the digital operator and the settings of B1-01 & B1-02.

O2-02 STOP Key During External Terminal Operation

B

Setting

Description

0

The digital operator STOP key is disabled when Run command does

not come from the digital operator (factory default).

1

The digital operator STOP key is always enabled.

The STOP key is enabled even during external terminal operation and

serial communication.

O2-04 Inverter Model Selection

A

Model

20P4

20P7

21P5

22P2

23P7

25P7

27P7

2011

2015

02-04

0

1

2

3

4

5

6

7

8

C6-02

(KHz)

8

8

8

8

8

8

8

8

8

L2-02 (sec)

0.7

1.0

1.0

1.0

2.0

2.0

2.0

2.0

2.0

Section O: Operator Parameters

O2 Key Selection