MotionWorks IEC Hardware Configuration – 2013-03-26

140

Hex Code

Description

ErrorClass

AxisErrorID

ErrorClass+AxisErrorID output from

MC_ReadAxisError

AlarmID

AlarmID output from Y_ReadAlarm

app

3407

0006

The file describing which configuration set to use was
corrupted. The default configuration set is being used.

app

3407

0007

An error occurred while writing a config file. The file
system may be full or damaged.

app

3407

0101

The configured RAM disk on the controller was unable
to be created.

app

3407

0102

Detected an unsupported option card inserted in the
controller.

app

3407

0104

Data in the controller SRAM did not match the expected
value. It should be treated as corrupted until it is re-
initialized.

app

3407

0106

The SRAM battery backup power failed. SRAM data
should be treated as corrupted until it is re-initialized.

app

3407

0107

The controller's time-of-day clock detected a voltage
decrease in the backup battery. The current time and
date is likely to be incorrect. This alarm can be cleared,
but will recur when the controller is powered ON until
the time and day is reset and the battery is replaced.

app

3407

0204

Unable to set configured network default gateway

app

3409

0001

The servo network axis node for the axis specified in
the configuration file was not found.

app

3409

0002

Axis enable failed. This problem is usually a result of
communication problems with the servo drive. It may
occur after a drive was disconnected from the
network. In this case, use Y_ResetMechatrolink to
establish communication with the drives once again.

app

3409

0003

Axis group motion activation failed. Some axes in the
group are currently under control of another group, or
motion has been blocked by the user.

app

3409

0004

The motion segment could not be added to the motion
queue because it is already queued.

app

3409

0005

Moves are prohibited when any of the group's axes are
disabled, have an alarm, or are in violation of their soft
limits.

app

340A

0001

The source for the logical input was not found, the
configured input will not be available.

app

340A

0002

The source for the logical output was not found, the