MotionWorks IEC Hardware Configuration – 2013-03-26

143

Hex Code

Description

ErrorClass

AxisErrorID

ErrorClass+AxisErrorID output from

MC_ReadAxisError

AlarmID

AlarmID output from Y_ReadAlarm

element to the analog I/O element.

app

340A

0020

One or more axes failed to respond to a servo-off
command during a system I/O initiated abort. This is
normally the result of communication problems with
the drive, which also causes an automatic servo-off.

app

340A

0022

Reset of a servo node failed.

app

340A

0023

The axis position may not be valid because the
persistent axis data was corrupted. SRAM should be
reinitialized and the axis should be homed.

app

340C

0000

All PLCopen error codes are in the range from 0x0000
to 0x0fff.

app

340C

0001

Time limit exceeded.

app

340C

0002

Distance limit exceeded.

app

340C

0003

Torque limit exceeded.

app

340C

0100

Modbus TCP I/O Driver Error on Server because of
invalid address range

app

340C

0101

MBTCP Client I/O driver, MBTCP Connection config is
missing input member

app

340C

0102

I/O memory area is not aligned to the correct byte to
accommodate reading and writing.

app

340C

0103

Watchdog Error

app

340C

0104

Reserved

app

340C

0106

Reserved

app

340C

0107

Reserved

app

340C

0108

Reserved

app

340C

0109

Reserved

app

340C

010A

Not enough memory on PLC for POU during insertion.
Project size must be reduced.

app

340C

010B

Internal PLC Error in memory management. This error
can occur if an older project was loaded on the
controller which was compiled to use lees of the
controllers total memory space. By using the
"Resource" Dialog box, perform "Delete On target," for
the bootproject, and then download the application
code again.

app

340C

010C

Internal PLC Error: POU invalid