6.5 Programming Example

6.5.4 Sending Request (Client)/Response (Server) according to Non-procedure Protocol

6-44

DB000210

TON[10ms]

Set

00300

Count DW00031

DB000211

DB000212

DB000202

DB000202

0013

0013
NL-1

DB000202

DB00021B

DB000400

0014

0019
NL-1

IF

DB000400==true

0015

0022
NL-1

INC

Dest DW00023

0016

0023
NL-2

END_IF

0017

0024
NL-1

DB000201

TON[10ms]

Set

00100

Count DW00030

DB000200

0018

0025
NL-1

DB000200

DB000211

DB000212

DB000202

DB000201

DB000201

0019

0028
NL-1

MSG-SND

Execute DB000201

Abort

DB000202

Dev-Typ 00014

Pro-Typ 00002

Cir-No

00001

Ch-No 00001

Param DA00000

Busy

DB000210

Complete DB000211

Error

DB000212

0020

0034
NL-1

IF

DB000211==true

0021

0035
NL-1

INC

Dest DW00024

0022

0036
NL-2

END_IF

0023

0037
NL-1

IF

DB000212==true

0024

0038
NL-1

INC

Dest DW00025

0025

0039
NL-2

STORE

Source DW00000

Dest

DW00026

0026

0040
NL-2

STORE

Source DW00001

Dest

DW00027

0027

0041
NL-2

END_IF

0028

0042
NL-1

END

0029

0043
NL-1

Abort command

Abort command

Abort command

Abort command

Normal

completion

Normal

completion

Abnormal

completion

Abnormal

completion

Abnormal completion

Forced stop if processing is not completed
within 3 seconds after sending the Send
command.

Increments the stop counter
when the Abort command is sent.

Starts sending every 1 second.

Function Send command

Turns ON after the query message is sent
and the response message is received.

Increments the normal pass counter.

Ended with transmission errors.

Increments the abnormal pass counter.

Stores the processing results.

Stores the status.

Normal completion

Start sending

Start sending

Command

Command

Command

Executing

Sends the command at intervals where
the receiving side can receive the command
properly. Because the command is sent in one
direction, adjustment is required so that the sent
command does not remain at the receiving side.

Sends a message to the remote station.
The executing coil turns ON when the CPU
receives the command.
The normal completion or abnormal completion
coil turns ON at the completion of processing.
Pro-Type: Always 2 (Non-procedure
communication)
Cir-No. (circuit number): 1 (Depends on the
connection port.)
Ch-No. (channel number): 1 (Use 1 to 10 for the
262IF-01.)

Advertising