6.1 Message Send Function

6.1.3 Inputs and Outputs for the Message Send Function

6-4

[ d ] Pro-Typ (Communication Protocol)

The Pro-Typ input specifies the communication protocol as shown in the following table.
Select 1 (MEMOBUS) or 2 (Non-procedure protocol 1) according to the type of an FL-net message.

The following table summarizes the correspondence between the FL-net message and Pro-Typ.

∗ 1. A response is returned by application receive processing (MSG-RCV function).The MSG-SND function is not

required.

∗ 2. Because the response is sent in the 262IF-01, no send processing by applications (MSG-SND function) is

required.

Œ

For the relationship between the FL-net message and message function, refer to 6.3 Combination of FL-net Mes-
sages and Message Functions
on page 6-29.

Type Code

Communication Protocol

Remarks

1

MEMOBUS

Select for word block read or word block write of FL-net messages.

2

Non-procedure 1
(in units of words)

Select for other than the above message.
Data will be sent in word units using the non-procedure protocol. No
response is received from the remote station.

3

Non-procedure 2
(in units of bytes)

Not used in FL-net.

Message Type

Function

Communication Protocol

Server

(Send

Response)

Client

(Send Request)

Word block read

Reads data in units of words.

*1

MEMOBUS

Word block write

Writes data in units of words.

*1

MEMOBUS

Network parameter read

Reads network parameter data.

*2

Non-procedure 1

Network parameter write

Writes network parameter data.

Not supported

Non-procedure 1

Stop command

Stops operation of equipment such as the PC connected
to the upper layer of the FA link protocol.

Not supported

Non-procedure 1

Start command

Starts operation of equipment such as the PC connected
to the upper layer of the FA link protocol.

Not supported

Non-procedure 1

Profile read

Reads a device profile.

*2

Non-procedure 1

Transparent message

Provides a transparent service to the upper layer of the
FA link protocol.

Non-procedure 1

Non-procedure 1

Log data read

Reads log data concerning a specified node.

*2

Non-procedure 1

Log data clear

Clears log data concerning a specified node.

*2

Non-procedure 1

Message loopback

Loops back a received message.

*2

Non-procedure 1