6.1 Message Send Function

6.1.5 Parameter Details for MSG-SND Function

6-12

COMMAND

The processing command for the MSG-SND function is output to these bits. The processing that is executed depends
on the setting of the COMMAND bits.

PARAMETER

The following error code is output if RESULT is set to 4 (FMT_NG: parameter format error). In other cases, the remote
node number is output.

( 3 ) PARAM02: Remote Node Number

Specifies the destination node number (1 to 254).

Œ

The details of the remote node information including node number can be checked on the Network Configuration

Window. Refer to 4.2.6 Network Configuration Window on page 4-13 for the Network Configuration Window.

( 4 ) PARAM04: Function Code (Only When Extended MEMOBUS Is Used)

PARAM04 sets the function code to be sent (setting is not required for non-procedure protocol).
The function registered to the function code is used by specifying the function code here. Functions include reading
coil and input relay status and writing holding registers.
The function codes used for the MEMOBUS or Extended MEMOBUS protocol are listed in the following table.

<Function Codes>

Œ

W: Word data

Π{

: Can be set,

×

: Cannot be set.

3

Code (Hex)

Abbreviation

Meaning

1

U_SEND

Send General-purpose Message with Non-procedure Protocol

2

U_REC

Receive General-purpose Message with Non-procedure Protocol

3

ABORT

Abort

8

M_SEND

Send MEMOBUS command; executing the command is completed upon receiving a response.

9

M_REC

Receive MEMOBUS command; executing the command is followed by sending a response.

C

MR_SEND

Send MEMOBUS response

4

RESULT Code

Meaning

RESULT = 4 (FMT_NG: pa-
rameter format error)

00

No errors

01

Remote node number out of range

02

MEMOBUS response receive monitor time error

03

Retry count setting error

04

Cyclic area setting error

05

CPU No. error

06

Data address error

07

Data size error

08

Function code error

Other values of RESULT

††

Remote node number

Function

Code

Applicable

Data Type

Function

Protocol Type

Extended

MEMOBUS

MEMOBUS

00H to 07H

Not used.

09H

W

Word block read

{

×

0AH

Not used.

0BH

W

Word block write

{

×

0CH to 10H

Not used.

Advertising