Appendix C FL-net System Grounding

C.4 Laying and Grounding a Wiring Duct and a Conduit

A-17

App

Appendices

C.4

Laying and Grounding a Wiring Duct and a Conduit

The following gives an example of laying and grounding a wiring duct and a conduit in FL-net as shown in Fig. C.5
and Fig. C.6.
Wiring must be performed as follows:

• When a wiring duct is used, the power lines and signal lines must be separated with separators according to

their levels. In addition, the wiring duct (including a cover and a separator) must be grounded with a ground
resistance of 100

Ω or less.

• When conduits are used, the conduits should be prepared individually for the power lines and signal lines

according to their levels. In addition, the conduit must be the one defined in JIS-C-8305 and must be grounded
with a ground resistance of 100

Ω or less.

Fig. C.5 Wiring Example via a Wiring Duct

Fig. C.6 Wiring Example via a Conduit

Separator

Wiring duct

Power line

I/O signal line

Analog I/O signal line

Communication cable

Ground of ground
resistance: 100

Ω or less

Conduit

Signal line

Ground of ground
resistance: 100

Ω or less