Chapter 7. PARAMETER SETUP

7-15

● D v -L (3-position control deviation lower limit)

● D v -H (3-position control deviation upper limit)

● H Y -L (3-position control lower limit hysteresis)

● H Y -H (3-position control upper limit hysteresis)

In 3-position control, control is carried out in the following three states in the RUN,
HOLD, FAST and END modes.

State

Heat-side Output

Cool-side Output

MV

1

OFF (0.0%)

ON (100.0%)

0.0%

2

OFF (0.0%)

OFF (0.0%)

50.0%

3

ON (100.0%)

OFF (0.0%)

100.0%

SP

PV

OFF

ON

OFF

ON

Output (heat)

Output (cool)

H Y - L

D V - L

D V - H

H Y - H

Even in 3-position control, output is time-proportional in the READY mode. This
is set in setup data

C

1

6

(MV (heat) in READY mode) and

C

1

7

(MV (cool) in

READY mode).

When connecting an actuator that may burn by time-proportional output, set setup
data

C

1

6

and

C

1

7

so that output in the READY mode is 0%.