Digital output test for control output (

00-04

)

Press

PARA key

until the PROG/SEG display shows (

00-04

).

When the digit of upper display is changed by

,

,

, or

keys

, the state of voltage

pulse or relay control output is changed as shown in Table 11-5.

Since the 6D hardware is of voltage pulse output (0D and 2G hardware is of relay) spec-

ification, the ON/OFF check must be performed in meeting with the specification.

Table 11-5.

Digital output test for event (

00-05

)

Press

PARA key

until the PROG/SEG display shows (

00-05

).

Table 11-6. DO

0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
0.0.1.0.
0.0.2.0.
0.0.4.0.
0.0.8.0.

ON

DO

Terminal
Number

Upper
Display

Notes: 1. “—” in the table means “OFF”.

2. Since the DO hardware is of open collector specification, the ON/OFF check must be performed in

meeting with the specification.

(4)

(5)

(6)

(7)

ON

(8)

(9)

ON

(49)

(55)

ON

(50)

(55)

ON

(51)

(55)

ON

(52)

(55)

ON

(53)

(55)

ON

0.0.0.0.

0.0.0.1.

0.0.0.2.

0.0.0.4.

Upper Display

State

All OFF

6D, 0D, 2G output
CH1 ON

6D, 2G output
CH2 ON

6D output
CH3 ON

11-9

Chapter 11. CALIBRATION