Chapter 5. FUNCTIONS

5-6

Time events 1 to 5

Either of time events or segment No. events can be selected by the time event type item
in the event configuration data setup.

Time events

Segment

1

ON time

OFF time

Output ON

Output OFF

ON<OFF

Segment

2

3

ON time

OFF time

Output ON

Output OFF

Output turns OFF at
end of segment even if
OFF time is not set.

Segment

5

6

ON time

OFF time

Output ON

Output OFF

ON
continued

Segment

3B

3C

ON time

OFF time

Output ON

Output OFF

No ON

ON=OFF ON>OFF

Segment

4

Segment time

5

ON time

OFF time

Output ON

Output OFF

G.Soak standby

ON-OFF time is invalid
even if set in excess of
segment 4 time.

Advance to
segment 5

ON=0

Segment

7

ON time

OFF time

Output ON

Output OFF

Segment time start

The ON and OFF times or only the ON time can
be set for each event No. and segment. The fol-
lowing describes ON/OFF of output.

• When the ON time is smaller than the OFF

time, output is ON for the duration from the
ON time to the OFF time.
(See segments 1, 6 and 7 in the figure.)

• When only the ON time is set, output is ON

for the during from the ON time to the seg-
ment end point.
(See segments 2 and 5 in the figure.)

• When both the ON time and OFF time are not

set, output is OFF.
(See segment 3 in the figure.)

• Setting only the OFF time without an ON time

is not possible.
(See segment 3B in the figure.)

• Setting an ON time to be greater to or equal

than the OFF time is not possible.
(See segment 3C in the figure.)

• Only ON and OFF times set within the seg-

ment time are valid. Times straddling the next
segment are invalid. The ON and OFF times
set in the next segment are valid.
(See segments 4 and 5 in the figure.)

Accordingly, the ON and OFF times settings
at the segment end point are ignored.

However, ON and OFF times set for segment
end points when the END mode is shifted to
are valid.
(See segment 9 in the figure, and compare with
segment 10 in the END mode.)

• When the ON time is set to 0 (no OFF time

setting, or OFF time is greater than 0), output
becomes OFF at time 0.

If output at the previous segment end point was
ON at this time, the output status at the seg-
ment switching point does not momentarily
become OFF.
(See segments 5 and 6 in the figure.)

• The G.Soak standby time is not included in the

ON and OFF times.
(See segment 7 in the figure.)