Chapter 4. WIRING

4-17

5-wire system RS-485 mutual connection

57

58

59

60

61

SDA

SDB

RDA

RDB

SG

FG

57

58

59

60

61

SDA

SDB

RDA

RDB

RDA

RDB

SDA

SDB

SG

FG

SG

FG

57

58

59

60

61

SDA

SDB

RDA

RDB

SG

FG

Terminating resistor

Terminating resistor

Terminating resistor

Terminating resistor

Slave station DCP301

Shielded cable

Shielded cable

Shielded cable

Master station

Slave station DCP301

Slave station DCP301

Provide terminating resistor of 150

Ω±

5%, 1/2W min. at both ends of the communications path.

Grounding of the shielded FG terminal should be carried out at only one end and not both ends.

Be sure to connect SG terminals each
others.
Failure to do so might cause unstable
communications.

Handling Precautions