Setting up time events 1 to 5 – Sonic Alert Digital Program Controller DCP301 User Manual

Page 135

Advertising
background image

Chapter 8. PROGRAM SETUP

8-8

Setting up time events 1 to 5

(1) In the setting display state, move to the event 1 to 5 items of the segment to be set up

on the programming map.

(2) If you press

ENT

, the upper display starts blinking to indicate start of entry to the

No.1 setup.

(3) Press

,

,

or

to set to the No.1 setup ON time setting.

Setting range: 0:00 to 99:59 (h:min/min:s)

0.0 to 599.9 (0.1s)

(Select either of h:min or min:s as the time unit in setup data

C 6 4. “:” is substituted by

“.” as it cannot be displayed.)

(4) When you press

ENT

, blinking on the upper display stops. The lower display then

starts blinking to indicate start of entry to the No.2 setup.

(When

FUNC

+

CLR

are pressed, the upper and lower displays both return to “- - - -”

and blinking stops.)

(5) Press

,

,

or

to set to the No.2 setup ON time setting.

Setting range:

ON time setting + 0:01 to 99:59 (h:min/min:s)
ON time setting + 0.1 to 599.9 (0.1s)

(6) When you press

ENT

, blinking on the upper display stops.

(When

FUNC

+

CLR

are pressed, the upper display returns to “- - - -” and stops blinking.)

Display

ON time setting value

OFF time setting value

Program No.

Segment No.

Pattern

tendency

LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out

• “- - - -” is displayed for the setting values in non-set segments.

• On models that do not support time events, event 1 to 5 items on the programming map

are all skipped and not displayed. The table below shows time events by a «.

• When setup data

C 6 Q is set to 1, event 1 to 5 items on the programming map are all

skipped and not displayed.

• When the ON time is set to 99:59, “- - - -” is displayed as the OFF time, and the display

does not blink.

• When the ON time is set higher than the time setting of the pattern item, event output

at that segment is OFF. However, note that event output is ON when the mode changes
to the END mode at segments whose ON time and pattern item time are equal.

Time event No.

TTTTT

TTTTT

setting value

T1

T2

T3

T4

T5

0

«

«

«

«

«

1

«

«

«

«

2

«

«

«

3

«

«

4

«

5