Sonic Alert Digital Program Controller DCP301 User Manual

Page 119

Advertising
background image

Chapter 7. PARAMETER SETUP

7-34

OFF

ON

20%

50%

40%

OFF

ON

20%

50%

40%

Setting=0

Setting=1

Cycle time

Cycle time

Cycle time

Cycle time

PID operation result

PID operation result

● C 6 5 (time display)

0: Remaining segment time

1: Total operation time

• This selects the time display in the basic display state in the program operation mode.

• When set to 0, in the READY mode, the time setting value of the currently selected

segment is displayed.

• When set to 0, in the RUN, HOLD, FAST or END modes, the remaining time for the

currently executing segment is displayed after being rounded down.

For example, if the remaining time is 1h, 30min, 59s when the time unit is set to “h:min”,
the time display is “

1 .3 0”.

• When set to 1, in the READY mode, the time display is “

0 .0 0”.

• When set to 1, in the RUN, HOLD, FAST or END modes, the time it takes to shift from

the READY to the RUN mode is displayed after being round down. Also, after

q q .5 q” the time display changes to “0 .0 0”.

For example, if the remaining time is 101h, 30min, 59s when the total operation time is
set to “h:min”, the time display is “

1 .3 0”.

• In the FAST mode, the time display changes according to the FAST scale if this pa-

rameter is set to either 0 or 1.

● C 6 6 (PV display)

This selects PV display in the basic display state. You can select between numerical
display or no display at all. The setting of this parameter does not influence PV-related
input processing, PID operation, event output, auxiliary output and alarm display.

Also, to eliminate PV alarm display or PV alarm event output, select the thermocouple
range by the input range to short-circuit the input terminals.

● C 7 2 (cold junction compensation)

0: Compensated internally

1: Compensated externally

• This selects how thermocouple cold junctions are to be compensated.

• When set to 1, carry out 0

°

C compensation by an ice box, for example.

● C 7 4 (voltage time-proportional output system)

0: Input ON again enabled within time-proportional cycle

1: Input ON again disabled within time-proportional cycle

• This selects whether or not to turn output ON again even if output is OFF when the

results of PID operation have changed during the time-proportional cycle (cycle time).

• The figure below shows each of these differences.