Cl r, P.l i n – Sonic Alert Digital Program Controller DCP301 User Manual

Page 139

Advertising
background image

Chapter 8. PROGRAM SETUP

8-12

Program No.

Segment No.

Pattern

tendency

EV1 to EV3 and T1 to T5 all out

C

L

R.

Setting up pattern link items

(1) In the setting display state, move to the pattern link items on the programming map.

(The settings are common to all segments as the pattern link items are setting items
provided for each program.)

(2) If you press

ENT

, the lower display starts blinking to indicate start of entry to the

No.1 setup.

(3) Press

,

,

or

to set to the No.1 setup pattern link setting.

Setting range: 0 to 19

0:Pattern link disabled
1 to 19: Pattern link destination program No.

(4) When you press

ENT

, blinking on the lower display stops.

Display

• The settings are common to all segments as the pattern link items are setting items

provided for each program.

• When setup data

C 7 1 is set to 1, pattern link items on the programming map are

skipped and not displayed.

Deleting programs

(1) In the setting display state, move to the pattern item of the segment from which the

program is to deleted on the programming map.
To delete all the segments of a particular program, move to the No.1 segment.

(2) If you press

ENT

, the upper display starts blinking to indicate start of entry to the

No.1 setup.
(So far, the procedure is the same as that for setting the pattern item.)

(3) If you press

FUNC

+

CLR

, the display changes to confirm clearing of the program, and

C L R .” is displayed blinking in the upper display.

(4) Press

ENT

to execute deletion of the program.

(5) The DCP301 returns to the setting display state, both the upper and lower displays

change to “- - - -” to indicate no setting.

Display

• In the above procedure,

FUNC

+

CLR

are pressed while entering values (SP setting value)

to the No.1 setup. However, the program can also be deleted by pressing

FUNC

+

CLR

while entering values (time setting value) to the No.2 setup.

• “- - - -” is displayed for the SP and time setting values in non-set segments.

• Currently running (RUN, HOLD, FAST, END) programs cannot be deleted.

Link destination program No.

Program No.

Segment No.

Pattern

tendency

EV1 to EV3 and T1 to T5 all out

P.L

I

N

Advertising