Description of event configuration data – Sonic Alert Digital Program Controller DCP301 User Manual

Page 107

Advertising
background image

Chapter 7. PARAMETER SETUP

7-22

Description of event configuration data

● E D 1 (event 1 standby)

● E D 2 (event 2 standby)

● E D 3 (event 3 standby)

0: Standby OFF

1: Standby ON

• When set to standby ON, event output becomes OFF if the controller is in the standby

state even if the condition for turning event output ON is satisfied.

• The controller enters the standby state in the following instances:

- When in the READY mode

- When shifting from the READY to the RUN mode

- When the power is turned ON

• The standby state is canceled in the following instances:

- When the condition for turning event output OFF (not including the hysteresis pe-

riod) is satisfied in one of the RUN, HOLD or FAST modes

- When set to standby OFF

• In the following example, PV event direct, operating point 500

°

C, hysteresis 10

°

C and

standby ON are set. When the mode changes from READY to the RUN mode at PV
550

°

C, the controller enters the standby state, so event output is turned OFF.

• Standby functions only when the event type is set to PV type event, and does not

function when set to time event type or controller status type.

● D L 1 (event 1 ON delay time)

● D L 2 (event 2 ON delay time)

● D L 3 (event 3 ON delay time)

• The ON delay time is processed after completing all processes up to event output standby

ON/OFF. Event output is turned ON when more than the ON delay time has elapsed
with the condition for turning event output ON satisfied.

• When the event type is set to ADV, the ON delay function does not operate whatever

value is set as the ON delay time.

• ON delay time is processed as follows.

ON delay time

Event ON conditions

Event output ON

Event OFF conditions

Event output OFF

Time

Event output OFF

Event OFF conditions