Chapter 10. SPECIFICATIONS

10-6

Item

Specification

General

Specifica-

tions

Display characters

Isolation

Memory backup

Rated power voltage

Power consumption

Power ON rush current

Power ON operation

Allowable transient power

loss

Insulation resistance

Dielectric strength

Standard conditions

Operating conditions

Installation mode

Applicable standards

Installation category

Pollution degree

Char. bit count

Format

Data length

11bits/character

1 start bit, even parity, 1 stop bit; or 1 start bit, no parity, and 2 stop

bits

8bits

All inputs and outputs are completely isolated.

RS-485 communications can be performed by connecting to a computer equipped with an RS-485 interface.

Ambient temperature

Ambient humidity

Rated power voltage

Power frequency

Vibration resistance

Impact resistance

Mounting angle

Altitude

Ambient temperature

range

Ambient humidity range

Rated power voltage

Power frequency

Vibration resistance

Impact resistance

Mounting angle

Memory

Battery backed-up RAM

Battery life

Controller power OFF

Approx. 3 years under standard conditions

Controller power ON

Approx. 10 years under standard conditions

90 to 264Vac, 50/60Hz

30VA max.

15A max., 10ms (under operating conditions)

When starting up a number of DCP31s simultaneously, ensure ample power is supplied

or stagger startup times. Otherwise, the controllers may not start normally due to inrush

current induced-voltage drop. Voltage must stabilize within 2s after power ON.

Reset time:

15s max. (time until normal operation possible under normal operating

conditions)

20ms max. (under operating conditions)

Min. 20M

Ω across power terminal (1) or (2) and ground terminal (3) (using a 500Vac

megger)

1500Vac 50/60Hz for 1min across power terminal and ground terminal

1500Vac 50/60Hz for 1min across relay output and ground terminal

500Vac 50/60Hz for 1min across non-power terminal and ground terminal

500Vac 50/60Hz for 1min across isolated terminals

23

±2°C

60

±5%RH

105Vac

±1%

50

±1Hz or 60 ±1Hz

0m/s

2

0m/s

2

Reference plane (vertical)

±3°

2000m max.

0 to 50

°C (temperature at case bottom when closely mounted)

10 to 90%RH (no condensation)

90 to 264Vac

50

±2Hz or 60 ±2Hz

0 to 1.96m/s

2

0 to 9.80m/s

2

Reference plane (vertical)

±10°

Handling Precautions

Permanently connected type controller, indoor installation, panel-mounted

EN61010-1, EN50081-2, EN50082-2 (CE statement), EN61326

Category II (IEC664-1, EN61010-1)