Heat/cool output (3d), Heat/cool output (5k), Voltage output (6d) – Sonic Alert Digital Program Controller DCP301 User Manual

Page 42: Handling precautions

Advertising
background image

Chapter 4. WIRING

4-10

11

12

13

SSR

2 to 22mAdc
With current adjustment function
(setup:

C78

)

Voltage output is reliant on an internal fixed-current circuit.

Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load.

Factory setting: general-purpose SSR voltage value.

Heat/cool output (3D)

Connect as follows.

11

12

13

14

15

16

Load

Power supply

Load

Power supply

Output 1
Contact rating, resistive load
5A (30Vdc/120Vac)
4A (240Vac)

Minimum switching current: 100mA

Output 2
Contact rating, resistive load
5A (30Vdc/120Vac)
4A (240Vac)

Minimum switching current: 100mA

When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (100mA min.).

Heat/cool output (5K)

Connect as follows.

11

12

13

(SSR)

14

15

16

(SSR)

Load

Load

Output 2

Output 1

• Voltage output:

2 to 22mAdc
With current adjustment function (setup:

C78

)

Current output:
4 to 20/0 to 20mAdc
Load resistance 600

max.

Voltage output:
2 to 22mAdc
With current adjustment function (setup:

C79

)

Current output:
4 to 20/0 to 20mAdc
Load resistance 600

max.

Voltage output (6D)

Connect as follows.

Current output and voltage output can be selected by setups

C

7

5

and

C

7

6

.

Voltage output is reliant on an internal fixed-current circuit.

Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load.

Factory setting: general-purpose SSR voltage value.

Handling Precautions

Handling Precautions

Handling Precautions