Chapter 4. WIRING

4-12

4-10 Connecting Event Output (relay output)

Event outputs EV1 and EV2 are 1a contact, and event output EV3 is 1a1b. Event outputs are connected on the
standard terminal base.

10

8

9

6

7

4

5

EV1 1a

EV2 1a

EV3 1a1b

Load

Power supply

Load

Power supply

Load

Power supply

Standard terminal base

Contact rating, resistive load
1A (30/250Vdc)

Contact rating, resistive load
1A (30/250Vdc)

Contact rating, resistive load
2A (30/250Vdc)

Minimum switching current: 10mA

When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (10mA min.).

Handling Precautions