The program is not advanced by pressing, Auto-tuning (at) is not started by pressing – Sonic Alert Digital Program Controller DCP301 User Manual

Page 146

Advertising
background image

Chapter 9. TROUBLESHOOTING

9-4

Press

RUN/HOLD

to set the controller to the RUN mode. (The

controller can be reset in case of external switch input
or communications even in the READY mode.)

Press

PROG

+

RUN/HOLD

to set the controller to the READY

mode, and press

RUN/HOLD

again to set the controller to the

RUN mode.

Set constant-value operation data

M

.O

D

E

setting to 0.

Set variable parameter

L

O

C

setting to 0 to 2.

The program is not advanced by pressing

PROG

+

DISP

in the basic display state

The controller is in the READY mode.

The controller is in the END mode.

The controller is in the constant-value opera-
tion mode.

Key lock is enabled.

Cause

Remedy

The controller does not change to FAST mode by pressing

FUNC

+

in the basic

display state

The controller is in the READY mode.

The controller is in the END mode.

The controller is in the constant-value opera-
tion mode.

Key lock is enabled.

Cause

Remedy

Press

RUN/HOLD

to set the controller to the RUN mode. (The

controller can be reset in case of external switch input
or communications even in the READY mode.)

Press

PROG

+

RUN/HOLD

to set the controller to the READY

mode, and press

RUN/HOLD

again to set the controller to the

RUN mode.

Set constant-value operation data

M

.O

D

E

setting to 0.

Set variable parameter

L

O

C

setting to 0 to 2.

The controller does not change to MANUAL mode by pressing

A/M

in the basic

display state

ON-OFF control is being carried out by 0D
and 6D outputs.

3-position-proportional control is selected by
3D output.

Key lock is enabled.

Cause

Remedy

Set PID set

P

setting in use to other than 0.0 and switch

to PID control from ON-OFF control.

Set setup data

C

4

5

setting to 0 and switch to PID

control from 3-position-proportional control.

Set variable parameter

L

O

C

setting to 0 to 2.

The controller does not change to AUTO mode by pressing

A/M

in the basic dis-

play state

Key lock is enabled.

Set variable parameter

L

O

C

setting to 0 to 2.

Cause

Remedy

The controller is in the READY mode.

The controller is in the MANUAL mode.

Input 1 over-range

Controller set not to execute AT.

The controller is set to programmer functions
by 5G output.

This is a heat/cool model.

Key lock is enabled.

Cause

Remedy

Press

RUN/HOLD

to set the controller to the RUN mode.

Press

A/M

to set the controller to the AUTO mode.

Correctly wire input 1 to correct input state.

Set variable parameter

A

T

setting to other than 0.

Set setup data

C

1

8

setting to 0.

AT cannot be executed by 3D and 5K outputs.

Set variable parameter

L

O

C

setting to 0 to 2.

Auto-tuning (AT) is not started by pressing

AT

in the basic display state