Chapter 7. PARAMETER SETUP

7-20

No.

Item Code

Item

Factory

User

Setting

Setting

Setting

9

E

T

3

0

10

E

D

3

0

11

H

Y

S

3

5

12

D

L

3

0

PV type events

0: PV direct

1: PV reverse

2: Deviation direct

3: Deviation reverse

4: Absolute value deviation1 direct

5: Absolute value deviation1 reverse

6: SP direct

7: SP reverse

8: MV direct

9: MV reverse

10: MFB

direct

11: MFB reverse

12 to 49: NOP

Time events

50: Time event

51 to 99: NOP

Controller status events

100: RUN+HOLD+FAST+END

101: READY

102: RUN

103: HOLD

104: FAST

105: END

106: G.Soak standby

107: MANUAL

108: Auto-tuning executing

109: Constant-value operation

110: MFB estimated position control

111: Sum of all alarms

112: PV range alarm

113: Controller alarm

114: Low battery voltage

115: Console setup in progress

116: Loader setup in progress

117: ADV (ON time 1s)

118 to 199: NOP

[Note]

Setting can be changed only in READY mode.

0: Standby OFF

1: Standby ON

[Note]

The controller stands by after power is restored and in

the READY mode. When the event type setting is

50,

“– – – –” is displayed and setting is not possible.

0 to 200U (when event type is neither MV nor MFB)

0.0 to 20.0% (when event type is MV or MFB)

[Note]

When the event type setting is

50, “– – – –” is

displayed and setting is not possible.

0 to 3600s

Event 3 type

Event 3 standby

Event 3 hysteresis

Event 3 ON delay

time