Chapter 7. PARAMETER SETUP

7-13

● D I F F

• ON-OFF control differential

When P is set to 0.0 on both 0D and 6D output models, control is set to ON-OFF control,
and operational period at that time is set.

Differential

gap

PV

OFF

ON

Reverse action

Differential

gap

PV

OFF

ON

Direct action

SP

SP

• Position-proportional control dead zone

On 2G output models, a dead zone between the motor open and motor closed positions is
set.
As a general guideline, the minimum value is the value where this dead zone changes to
stop motor hunting once a fixed value set to manual output is being output.
If this value is set without any margin, the motor will be operating at all times, which will
considerably shorten its service life.
The factory setting is 5%. Use this as a guideline, and take the control results and motor
service life into consideration when setting the dead zone.

MFB (%)

*

Dead zone

Open-side

relay ON

Closed-side

relay ON

Control output (%)

*: Dead zone setting value

*

• Heat/cool control dead zone

On heat/cool models, this sets how the relationship between heat-side output and cool-
side output should be processed with respect to the MV resulting from PID operation.
Heat-cool control is calculated as follows:

PV

SP

Heat-side
output

Cool-side
output

MV

(PID operation result)

Dead zone

Heat-cool output calculation

PID set selection

(1 of 4 sets)

Heat-side PID set
Constants

OL

,

OH

Constants

P

,

I

,

D

,

Re

PID operation

(fixed to reverse action)

Cool-side

PID set

Heat-side

PID set

Cool-side PID set
Constants

OL

,

OH

Note 2)

Note 4)

Note 3)

Note 1)