Handling precautions – Sonic Alert Digital Program Controller DCP301 User Manual

Page 123

Advertising
background image

Chapter 7. PARAMETER SETUP

7-38

(2) Turn the DCP301 ON again, and set setup data

C q 0 setting to 241. For details on

how to change settings, see 7-1 Parameter Setup (page 7-1).

(3) Display the setup data

C q 1 setting.

(4) Press

ENT

to display the difference (A—B) between the resistances of the Zener bar-

rier connected to leads A and B on the lower display.

(5) Press

ENT

to memorize the difference (A—B) between the resistances to the control-

ler.

(6) Press

DISP

to set the DCP301 to the basic display state.

(7) Turn the power OFF, and remove the short across A and B.

• The resistance error of the Zener barrier connected to leads A and B cannot be

adjusted unless it is 20

or less.

• This adjustment is not required when a Zener barrier and an input other than

an RTD are not used.

• Once the Zener barrier has been adjusted, compensation is carried out on the

Zener barrier. When using on an RTD without a Zener barrier, re-adjust without
the Zener barrier.

32

33

34

C

B

A

Zener barrier

Zener barrier

Zener barrier

DCP301

Short-circuit

● C

q

1 (Input 1 Zener barrier adjustment)

The following adjustment must be made when using a Zener barrier.

(1) Turn the DCP301 OFF. When you have finished mounting and wiring the DCP301,

short-circuit across A and B on the terminals of the RTD.

Handling Precautions

Advertising