Sonic Alert Digital Program Controller DCP301 User Manual

Page 176

Advertising
background image

Cold junction sensor calibration

Scroll

,

,

, or

keys

to show (

2.0.2.2.

) on upper display, then press

ENT

key

.

The cold junction input 0%

(1) Press

SETUP key

until the PROG/SEG display shows (

02-01

).

(2) Press

ENT key

after display stabilizes, AD count is shown on lower display.

The cold junction AD count data

(1) Press

SETUP key

until the PROG/SEG display shows (

02-02

).

(2) Press

ENT key

after display stabilizes, AD count is shown on lower display.

The cold junction temperature data

(1) Press

SETUP key

until the PROG/SEG display shows (

02-03

).

(2) Connect the thermometer (55).

(3) Scroll

,

,

, or

keys

to set above temperature value(°C).

(4) Press

ENT key.

Current output calibration

Scroll

,

,

, or

keys

to show (

4.0.4.4.

) on the upper display, then press

ENT

key

.

Connect the digital ammeter across terminals (See Figure 11-9).

OUT CH1 output calibration

(1) Press

PARA key

until the PROG/SEG display shows (

04-01

).

Scroll

,

,

, or

keys

until meter indicates 4.00mA, then press

ENT key

.

(2) Press

PARA key

until the PROG/SEG display shows (

04-02

).

Scroll

,

,

, or

keys

until meter indicates 20.00mA, then press

ENT key

.

OUT CH2 output calibration

(1) Press

PARA key

until the PROG/SEG display shows (

06-03

).

Scroll

,

,

, or

keys

until meter indicates 4.00mA, then press

ENT key

.

(2) Press

PARA key

until the PROG/SEG display shows (

06-04

).

Scroll

,

,

, or

keys

until meter indicates 20.00mA, then press

ENT key

.

OUT CH1 output calibration

(1) Press

PARA key

until the PROG/SEG display shows (

04-05

).

Scroll

,

,

, or

keys

until meter indicates 4.00mA, then press

ENT key

.

(2) Press

PARA key

until the PROG/SEG display shows (

04-06

).

Scroll

,

,

, or

keys

until meter indicates 20.00mA, then press

ENT key

.

11-12

Chapter 11. CALIBRATION