Chapter 7. PARAMETER SETUP

7-41

(A

2

, B

2

)

(A

1

, B

1

)

B-axis

A-axis

1

2

3

4

5

6

7

9

8

10

11

B-axis (output)

Fixed value

(10000, 10000)

A-axis (input)

Fixed value

(-2000, -2000)

(A

3

, B

3

)

(A

2

, B

2

)

(A

1

, B

1

)

(A

3

, B

3

)

(A

2

, B

2

)

(A

1

, B

1

)

B-axis

B-axis

A-axis

A-axis

Excluded

Description of table data settings

● t -A . 1 to t -A . b

● t -b . 1 to t -b . b

• These settings are for the A-axis (input) and B-axis (output) settings of input 1 linear-

ization table approximation.

• Both ends of the linearization table are fixed at -2000U, -2000U and 10000U,10000U.

The linearization table is formed by connecting 11 points of table data settings be-
tween the two ends.

• Table data is set not by percentages but directly by engineering unit. When the range

type is set to linear, set scaled values.

• Points on the broken-line, An and Bn, must be set so that they increase in the following

way (A

1

, B

1

) = (0, 0), (A

2

, B

2

) = (100, 100) and so forth. If set points break this relation-

ship, the point in conflict must be excluded to create the linearization table.

• When two equal points such as A

1

and A

2

are set for the A-axis, B

1

shall be taken as the

output value.