Chapter 7. PARAMETER SETUP

7-39

● C

9

3 (CPL communications port selection)

• When set to 0, CPL communications from the loader jack is not possible. In this case,

CPL communications is possible from the addon terminal under setup

C 8 4 and C 8 5

communications conditions if the controller model supports CPL communications.

• When set to 1 to 15, CPL communications from the loader jack is not possible, and the

C 9 3 setting becomes the CPL communications address.

Communications conditions are also 4800bps, even parity and 1 stop bit.

In this case, CPL communications is not possible from the addon terminal even if the
controller model supports CPL communications.

• Use the special cable to connect the RS-232C port on the personal computer and the

loader jack on the equipment.

• When the setup

C 0 0 (ROM revision) setting indication is 0 or 1, the setup C 9 3

setting indication cannot be set at “---”.

Also, communications from the loader jack is not possible.