background image

Chapter 9. TROUBLESHOOTING

9-3

The controller is in the READY mode.

Key lock is enabled.

Press

RUN/HOLD

to set the controller to the RUN mode. (The

controller can be reset in case of external switch input or
communications even in the READY mode.)

Set variable parameter

L

O

C

setting to 0 to 2.

The controller is in the READY or FAST mode.

The controller is in the END mode.

The controller is in the constant-value opera-
tion mode.

Key lock is enabled.

Set all external switch inputs RSW8 to 12 OFF.

Reset the controller.

Set constant-value operation data

M .O

D

E

setting to 0.

Press

DISP

.

Set variable parameter

L

O

C

setting to 0 to 2.

Cause

Remedy

Program selection by external switch input not
0.

The controller is not in the READY mode.

The controller is in the constant-value opera-
tion mode.

Key lock is enabled.

9-2

Trouble during Key Entry

The program No. does not change by pressing

PROG

in basic display state

The program No. does not change by pressing

in the basic display state

Cause

Remedy

Program selection by external switch input not
0

The controller is not in the READY mode.

The controller is in the constant-value opera-
tion mode.

Entry changeable display state by
in MANUAL mode

Key lock is enabled.

Set all external switch inputs RSW8 to 12 OFF.

Reset the controller.

Set constant-value operation data

M .O

D

E

setting to 0.

Set variable parameter

L

O

C

setting to 0 to 2.

The controller does not change to RUN mode by pressing

RUN/HOLD

in the basic display

state

The currently selected program in READY
mode has not been set up.

The controller is in the END mode.

Key lock is enabled.

Select an already set up program.

Reset the controller to READY mode.

Set variable parameter

L

O

C

setting to 0 to 2.

Cause

Remedy

The controller does not change to HOLD mode by pressing

RUN/HOLD

in the basic dis-

play state

RUN mode is entered from READY or FAST mode. Press
RUN/HOLD key again.

Reset the controller to READY mode, and press

RUN/HOLD

twice.

Set constant-value operation data

M .O

D

E

setting to 0.

Set variable parameter

L

O

C

setting to 0 to 2.

Cause

Remedy

The controller cannot be reset by pressing

PROG

+

RUN/HOLD

in the basic display state

“Reset in the program operation mode” refers to switching to the READY mode and
returning to the No.1 segment.

“Reset in the constant-value mode” refers to switching to the READY mode.

Cause

Remedy

Advertising