Chapter 10. SPECIFICATIONS

10-5

Item

Specification

Event/

Time

Event

Output

Commu-

nications

Events 1, 2

Event 3

Time events 1 to 5

Event 1 to 3 settings

Time event 1 to 5 settings

Communications system

Interface system

Relay contact

output

Relay contact

output

Open-collector

output

Event type

Event standby

Event hysteresis

Event ON delay

Time event type

Communications

standard

Network

Data flow

Synchronization

Transmission

system

Data line

Signal line

Transmission speed

Transmission

distance

Other

Contact type:

1a

Contact rating:

1A (240Vac/30Vdc, resistive load)

Life:

100,000 operations (at rating)

Min. switching voltage, current:

10V, 10mA

Contact type:

1a1b

Contact rating:

2A (240Vac/30Vdc, resistive load)

Life:

100,000 operations (at rating)

Min. switching voltage, current:

10V, 10mA

External supply voltage:

10 to 29Vdc

Max. load current:

70mA/load

OFF leakage current:

0.1mA

ON residual voltage:

1.6V max.

PV type events:

PV, deviation, absolute value

deviation, SP, MV, MFB

Controller status events:

RUN+HOLD+FAST+END, READY,

RUN, HOLD, FAST, END, G.Soak

standby, MANUAL, auto-tuning

executing, constant-value operation,

MFB estimated position control, sum

of all alarms, PV range alarm,

controller alarms, low battery voltage,

setting on console, ADV

Time events

ON/OFF selectable

0 to 200U (event types PV, deviation, absolute value deviation

or SP)

0.0 to 20.0% (event types MV or MFB)

0 to 3600s

Time events, segment No. events

RS-485

Multidrop (DCP301 provided with only slave node functionality)

1 to 31 units max.

Half duplex

Start-stop synchronization

Balanced (differential)

Bit serial

5 transmit/receive lines (3-wire connection also possible)

4800, 9600bps

500m max. (total)

Conforming to RS-485