Chapter 8. PROGRAM SETUP

8-6

Setting up events 1 to 3 items

When event type is PV type event

(1) In the setting display state, move to the event 1 to 3 items of the segment to be set up

on the programming map.

(2) If you press

ENT

, the upper display starts blinking to indicate start of entry to the

No.1 setup.

(3) Press

,

,

or

to set to the No.1 setup event operating point setting.

Setting range: -1999 to 9999U

0 to 9999U (in case of absolute value deviation event)

-10.0 to 110.0% (in case of MV, MFB event)

(4) When you press

ENT

, blinking on the upper display stops.

(When

FUNC

+

CLR

are pressed, the upper display returns to “- - - -” and stops blink-

ing.)

Display (PV type event)

Operating point setting value

Program No.

Segment No.

Pattern

tendency

LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out

• “- - - -” is displayed for the setting values in non-set segments.

• When setup data

C 6 8 is set to 1, event 1 to 3 items on the programming map are

skipped and not displayed.