3 parameter setup list – Sonic Alert Digital Program Controller DCP301 User Manual

Page 92

Advertising
background image

Chapter 7. PARAMETER SETUP

7-7

No.

Item Code

Item

Factory

User

Setting

Setting

Setting

1

L O C

0

2

P R T C

0

3

F L

0.0

4

P B 1

0U

5

S B 1

0U

6

O T L

0.0

7

1 O U T

0.0

(50.0)

8

R P 1 D

0

9

A

T

0

10

S T

0

11

2 P 1 D

0

0: Key lock disabled

1: Display of setup data settings disabled

2: Display of parameter settings and program settings

disabled

3: Use of operation keys disabled

4: Display of parameter settings and program settings

displayed, and use of operation keys disabled

[Note]

Two or more key lock setting values for actual key lock

items and items assigned to can be displayed

and set.

0: Changing program settings enabled

1: Changing program settings disabled

0.0 to 120.0s

[Note]

0.0 disables the filter.

-1000 to 1000U

-1999 to 9999U
0.0 to 10.0% (0.1%s steps)
[Note]

0.0 disables the limit.

0.0 to 100%

[Note]

On heat/cool models, the factory setting is 50.0.

0: Automatic judgment of initialization is carried out by

advance operation.

1: Initialization is carried out by advance operation.

2: Initialization is not carried out by advance operation.

0: AT is disabled.

1: General AT is executed.

2: Overshoot-inhibited AT is executed.

3: AT by neural net is executed.

[Note]

On heat/cool models, “– – – –” is displayed, and

setting is not possible.

0: Smart-tuning is disabled.

1: The brake value is fixed to inhibit overshoot.

2: Overshoot is inhibited while automatically reviewing

the brake value.

[Note]

On heat/cool models, “– – – –” is displayed, and

setting is not possible.

0: 2 degrees of freedom PID is disabled.

1: 2 degrees of freedom PID is enabled.

[Note]

On heat/cool models, “– – – –” is displayed, and

setting is not possible.

PARA

Key lock

Program protect

Input 1 digital filter

Input 1 bias

SP1 bias

MV change limitter

(CH1)

PID operation initial

MV (CH1)

PID operation

initialization

Auto-tuning method

selection (CH1)

Smart-tuning

method selection

(CH1)

Advanced PID

selection (CH1)

7-3

Parameter Setup List

“U” and “%FS” used in the “Factory Setting” and “Setting” columns in the table mean
the following:

U:

The decimal point changes according to the input range type setting. For example,
when one digit past the decimal point is allowed, -1999U becomes 199.9, and
9999U becomes 999.9.

%FS: The numbers and decimal point position changes according to the input range setting.

For example, when the input range is 0.0 to 800.0

°

C, 0%FS is 0.0 and 100%FS is

800.0.

Variable parameter settings “

P

A

R

A

Note