Chapter 2. NAMES & FUNCTIONS OF PARTS

2-9

dc current, dc voltage

Input Format

Range No.

Code

Range (programmable)

4 to 20mA

64

C01

0 to 20mA

65

C08

0 to 10mA

66

M01

-10 to +10mV

67

L02

0 to 100mV

68

L01

-1999 to 9999

0 to 1V

69

L04

-1 to +1V

70

L08

1 to 5V

71

V01

0 to 5V

72

L05

0 to 10V

73

L07

• The unit of code Z06 is Kelvin (K)

• The lower limit readout of code B18 is 20

°

C (68

°

F).

The lower limit readout (

°

C) of codes K44, K46, T44, Z08 and Z07 is -199.9

°

C.

• The lower limit readout (

°

C) of codes F50, F46, P50 and P46 is -199.9

°

C.

• The upper limit readout (

°

C) of codes F01 and P01.

• The PV lower limit alarm does not occur with code F50.

However, note that the PV lower limit alarm occurs at a disconnection when
input has been downscaled when input is disconnected during setup.

• The number of digits past the decimal point for dc current and dc voltage is

programmable within the range 0 to 3.

Handling Precautions