Sonic Alert Digital Program Controller DCP301 User Manual

Page 172

Advertising
background image

Display test (

00-02

)

Press

PARA key

until the display test starts.

Then, each 7-segment LED, LED indicators and LCD illuminates at every 0.5 sec.

This is to check if each LED/LCD illuminates.

Digital input test (

00-03

)

Press

PARA key

until the PROG/SEG display shows (

00-03

).

When you turn on or off each remote switch, the upper display will show the data

described in Table 11-4.

Table 11-4. DI

0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
0.0.1.0.
0.0.2.0.
0.0.4.0.
0.0.8.0.
0.1.0.0.
0.2.0.0.
0.4.0.0.
0.8.0.0.

ON

DI

Terminal
Number

Upper
Display

Notes: 1. “ON” means to short the terminals by a jumper.

2. “—” means to open the terminals.

Example:

(21)

(25)

(22)

(25)

ON

(23)

(25)

ON

(24)

(25)

ON

(41)

(25)

ON

(42)

(25)

ON

(43)

(25)

ON

(44)

(25)

ON

(45)

(25)

ON

(46)

(25)

ON

(47)

(25)

ON

(48)

(25)

ON

(21)

(25)

ON

= Short (21) and (25) terminals.

11-8

Chapter 11. CALIBRATION

Advertising