Sonic Alert Digital Program Controller DCP301 User Manual

Page 115

Advertising
background image

Chapter 7. PARAMETER SETUP

7-30

No.

Item Code

Item

Factory

User

Setting

Setting

Setting

50

C

5

0

0

51

C

5

1

1000

52

C

5

2

0

53

C

5

3

0

54

C

5

4

0

55

C

5

5

1000

56

C

5

6

1000

57

C

5

7

1000

58

C

5

8

1000

59

C

5

q

1000

60

C

6

0

1000

61

C

6

1

1000

62

C

6

2

1000

63

C

6

3

0

64

C

6

4

0

65

C

6

5

0

66

C

6

6

0

-1999 to 9999U

-199.9 to 999.9%

[Note]

When the auxiliary output type is MV or MFB, the unit is

%. Otherwise, the unit is U.

0: NOP

1: Fast operation

2: PV start

3: NOP

4: AT start/stop

5: NOP

6: Manual/auto operation

7: Cancel G.Soak by OR conditions

8: Cancel G.Soak by AND conditions

9: Direct/reverse action inversion

10 to 20: NOP

[Note]

On external switch 4-input models, “– – – –” is dis-

played and setting is not displayed.

When the same assignment is set to two or more RSWs,

the RSW setting with the lowest No. is valid.

When this setting is set to NOP, the controller state is

not switched by external switch input ON/OFF. The

controller state can be switched ON/OFF by communi-

cations.

1000 to 5000

[Note]

To set the No., add the No. of the item to be assigned

to

PARA

to the following values for the setting group

containing that item.

• 1000:

Constant-value operation data

• 1500:

PID parameter

• 2500:

Variable parameter

• 3500:

Event configuration data

• 4000:

Table data

• 4500:

Setup data

Assignments to which a nonexistent No. have been set

are invalid.

0: READY

1: END

0: h/min

1: min/s

0: Remaining segment time

1: Total operation time

[Note]

The total operation time returns to 0 in the READY mode.

0: ON

1: OFF

2: ON

3: OFF
[Note]

Settings 0 and 2, and 1 and 3 mean the same, respec-

tively.

Auxiliary output 2

lower limit (4mA)

Auxiliary output 2

lower limit (20mA)

External switch

input RSW5

assignment

External switch

input RSW6

assignment

External switch

input RSW7

assignment

PARA

assignment

item 1

PARA

assignment

item 2

PARA

assignment

item 3

PARA

assignment

item 4

PARA

assignment

item 5

PARA

assignment

item 6

PARA

assignment

item 7

PARA

assignment

item 8

Operation comple-

tion state

Program time unit

Time display

PV display